在工業(yè)自動(dòng)化與數(shù)據(jù)中心建設(shè)高速發(fā)展的背景下,機(jī)箱機(jī)柜作為電子設(shè)備的物理載體,其穩(wěn)定性直接關(guān)系到系統(tǒng)運(yùn)行的可靠性。山東地區(qū)因氣候特點(diǎn)與工業(yè)環(huán)境差異,機(jī)箱機(jī)柜的維護(hù)需結(jié)合地域特性制定針對(duì)性方案。本文從基礎(chǔ)維護(hù)、環(huán)境適應(yīng)、檢測(cè)三個(gè)維度,詳細(xì)闡述科學(xué)維護(hù)流程。
Against the backdrop of rapid development in industrial automation and data center construction, the stability of chassis cabinets, as the physical carriers of electronic equipment, directly affects the reliability of system operation. Due to the differences in climate and industrial environment in Shandong region, targeted maintenance plans for chassis and cabinets need to be developed based on regional characteristics. This article elaborates on the scientific maintenance process from three dimensions: basic maintenance, environmental adaptation, and professional testing.
一、基礎(chǔ)維護(hù):清潔與結(jié)構(gòu)檢查
1、 Basic maintenance: cleaning and structural inspection
表面清潔與防塵
Surface cleaning and dust prevention
每周使用干燥的超細(xì)纖維布擦拭機(jī)柜表面,門板、頂蓋、側(cè)板的積塵。對(duì)于縫隙處的頑固污漬,可搭配軟毛刷清理,嚴(yán)禁使用含腐蝕性化學(xué)成分的清潔劑。某通信基站因長期使用酒精擦拭機(jī)柜漆面,導(dǎo)致涂層脫落生銹,后改用中性清潔劑后問題得到解決。
Use a dry microfiber cloth to wipe the surface of the cabinet every week, with a focus on removing dust from the door panels, top cover, and side panels. For stubborn stains in crevices, they can be cleaned with a soft bristled brush. It is strictly prohibited to use cleaning agents containing corrosive chemicals. A certain communication base station used alcohol to wipe the paint surface of the cabinet for a long time, causing the coating to peel off and rust. After switching to a neutral cleaner, the problem was solved.
每季度對(duì)進(jìn)風(fēng)口、排風(fēng)扇濾網(wǎng)進(jìn)行高壓氣槍吹掃或水洗,確保散熱通道暢通。山東沿海地區(qū)需增加清潔頻次,防止鹽霧沉積。
Perform high-pressure air gun blowing or water washing on the air inlet and exhaust fan filters every quarter to ensure smooth heat dissipation channels. The coastal areas of Shandong need to increase the frequency of cleaning to prevent salt spray deposition.
緊固件與門鎖檢查
Inspection of fasteners and door locks
每月檢查鉸鏈、鎖具、螺絲的緊固狀態(tài),使用扭矩扳手按標(biāo)準(zhǔn)值復(fù)緊。某制造企業(yè)因機(jī)柜門鎖松動(dòng),導(dǎo)致設(shè)備誤觸停機(jī),后建立“紅黃綠”三色標(biāo)識(shí)制度,對(duì)松動(dòng)部件即時(shí)標(biāo)記處理。
Check the fastening status of hinges, locks, and screws every month, and use a torque wrench to tighten them according to standard values. A manufacturing enterprise established a "red, yellow, and green" three color identification system to immediately mark and handle loose parts due to equipment shutdown caused by loose cabinet door locks.
對(duì)滑動(dòng)軌道、理線架等運(yùn)動(dòng)部件加注潤滑脂,使用耐高溫、抗氧化的二硫化鉬潤滑劑。
It is recommended to use high temperature resistant and anti-oxidation molybdenum disulfide lubricant when adding lubricating grease to moving parts such as sliding tracks and cable racks.
二、環(huán)境適應(yīng)性維護(hù)
2、 Environmental adaptability maintenance
溫濕度控制
Temperature and humidity control
山東夏季高溫高濕,需確保機(jī)柜內(nèi)溫度控制在25℃±3℃,濕度≤60%。某數(shù)據(jù)中心通過加裝機(jī)柜級(jí)空調(diào),將單機(jī)柜功耗下降,避免因過熱引發(fā)的設(shè)備宕機(jī)。
Shandong has high temperatures and humidity in summer, so it is necessary to ensure that the temperature inside the cabinet is controlled at 25 ℃± 3 ℃ and the humidity is ≤ 60%. A data center has installed cabinet level air conditioning to reduce the power consumption of individual cabinets and avoid equipment downtime caused by overheating.
冬季低溫環(huán)境下,檢查加熱模塊工作狀態(tài),防止冷凝水結(jié)冰損壞電路板。
In low temperature environments during winter, check the working status of the heating module to prevent condensation water from freezing and damaging the circuit board.
防雷與接地檢測(cè)
Lightning protection and grounding detection
每半年檢測(cè)接地電阻值,確?!?Ω。某風(fēng)電場(chǎng)因接地不良導(dǎo)致雷擊損壞設(shè)備,后采用銅包鋼接地極將電阻降標(biāo)準(zhǔn)值以下。
Check the grounding resistance value every six months to ensure it is ≤ 4 Ω. A wind farm suffered equipment damage from lightning strikes due to poor grounding, and subsequently used copper-clad steel grounding electrodes to reduce the resistance below the standard value.
檢查浪涌保護(hù)器狀態(tài)指示燈,對(duì)失效器件即時(shí)更換。
Check the status indicator light of the surge protector and replace any faulty components immediately.
三、檢測(cè)與預(yù)防性維護(hù)
3、 Professional testing and preventive maintenance
電氣檢測(cè)
Electrical safety testing
每年使用紅外熱成像儀掃描電源模塊、接線端子,提前發(fā)現(xiàn)過熱隱患。某化工廠通過該技術(shù)提前3個(gè)月發(fā)現(xiàn)接線松動(dòng),避免火災(zāi)事故。
Every year, use an infrared thermal imaging device to scan power modules and wiring terminals to detect potential overheating hazards in advance. A certain chemical plant discovered loose wiring three months in advance through this technology to avoid fire accidents.
檢測(cè)絕緣電阻,要求≥100MΩ,對(duì)老化線纜進(jìn)行更換。
Detect insulation resistance, requiring ≥ 100M Ω, and replace aged cables.
結(jié)構(gòu)強(qiáng)度評(píng)估
Structural strength assessment
對(duì)承載超過500kg的機(jī)柜,每兩年進(jìn)行承重測(cè)試。某物流倉庫因貨架超載導(dǎo)致機(jī)柜變形,后增設(shè)支撐梁并限制載荷。
For cabinets carrying over 500kg, load testing shall be conducted every two years. A logistics warehouse experienced cabinet deformation due to overloaded shelves, and subsequently added support beams to limit the load.
檢查抗震支架的螺栓預(yù)緊力,確保符合當(dāng)?shù)乜拐鹪O(shè)防要求。
Check the bolt preload of the seismic support to ensure compliance with local seismic design requirements.
四、特殊場(chǎng)景維護(hù)方案
4、 Special scenario maintenance plan
沿海腐蝕環(huán)境
Coastal corrosive environment
對(duì)金屬部件每季度檢查銹蝕情況,采用三步除銹法:砂紙打磨→除銹劑清洗→環(huán)氧富鋅底漆涂裝。某港口企業(yè)通過該流程使機(jī)柜壽命延長。
Quarterly inspection of rust on metal components using a three-step rust removal method: sandpaper polishing → rust remover cleaning → epoxy zinc rich primer coating. A certain port enterprise has extended the lifespan of its cabinets through this process.
更換不銹鋼材質(zhì)的鉸鏈、鎖具,提升耐蝕性。
Replace hinges and locks made of stainless steel material to enhance corrosion resistance.
粉塵污染環(huán)境
Dust pollution environment
在進(jìn)風(fēng)口加裝初效+中效雙層濾網(wǎng),過濾效率達(dá)90%以上。某面粉廠采用該方案后,機(jī)柜內(nèi)部清潔周期延長。
Install a dual layer filter with primary and medium efficiency at the air inlet, achieving a filtration efficiency of over 90%. After a flour mill adopted this plan, the cleaning cycle inside the cabinet was extended.
配置正壓送風(fēng)系統(tǒng),維持柜內(nèi)氣壓高于外部環(huán)境,防止粉塵侵入。
Configure a positive pressure air supply system to maintain the air pressure inside the cabinet higher than the external environment and prevent dust from entering.
This article is a friendly contribution from Shandong MNS low-voltage drawer cabinet For more information, please click: http://m.shyhjx021.com We will provide detailed answers to your questions. You are welcome to log in to our website and leave a message